Product description
Fusible Link - Model K | RS Steel

This product is designed specifically for range hood protection. The K Fusible Link is listed by Underwriters Laboratories, Inc.
For Kidde Systems
Used For Fire Protection
Listed by Underwriters Laboratories, Inc.
Mechanical Heat Activated Device
Maximum Load = 50 lbs. (22.68 kg.)
Minimum Load = 3 lbs. (1.36 kg.)
Corrosion Resistant Construction
Bronze Components
Broad Load Range
Solid Eye-to-Eye Connection
SKU | Degree |
---|---|
FLG165K | 165 |
FLG212K | 212 |
FLG280K | 280 |
FLG360K | 360 |
FLG450K | 450 |
ADDITIONAL NOTES
Maintenance, inspection and replacement of fusible links utilized in range hood fire protection.
NFPA Bulletin 96 section 11.4.7 indicates, "Cleaning Chemicals shall not be applied on fusible links". Globe Technologies Corporation strongly recommends that the Fusible Links be wiped and cleaned with a wet cloth between routine servicing and replacement and not by the application of cleaning chemicals or steam.
Where code requires replacement.
Replacement schedules: NFPA BULLETINS: 96, 17 AND 17 A. Mandate semi-annual service and replacement .To ensure you do not experience premature activation and or failure does not occur. Globe Technologies strongly advise more frequent replacement in situations of heavy usage or where local cleaning as mentioned previously may take place.
As a life safety and property protection system, both premature and actual activation can be a costly action solved by adherence to this information. Mandate replacement of fusible links at least semi annually.